Product Description:
YBP (M) 3B-12/0.4 High/Low Voltage Pre-installed Substation (referred to as Box Substation) is an equipment that high-voltage power collection, transformer voltage reduction, and low-voltage distribution etc are organically combined, installed in a moisture-proof, dust-proof, animal proof, fireproof, anti-theft, heat-insulating, sealed and movable steel box. The function of mechatronics and enclosed operation, especially suitable for urban network construction and transformation, is a new substation after the civil engineering substations.
The box substation has mechanical and electrical interlocking. The substation meets the requirements of "five prevention" and has complete functions of monitoring, control, and protection.
The box substation has the characteristics of strong completeness, small size, compact structure, safe and reliable operation, convenient maintenance, and mobility. Compared with conventional civil engineering substations, box substation of the same capacity usually occupy only 1/10 to 1/5 of the area of conventional substations, greatly reducing design workload and construction costs. In the distribution system, it can be used for ring network distribution systems, as well as dual power or radial terminal distribution systems. It is a new type of complete equipment for the construction and renovation of urban and rural substations.
Technical parameters:
No. | Component name | Unit | Technical parameter | ||||
1 | Rated frequency | Hz | 50 | ||||
2 | Rated voltage | KV | 7.2 | 12 | |||
High voltage unit | 1min power-frequency withstand voltage | phase-phase, phase-earth | 32 | 42 | |||
Isolation fracture | 36 | 48 | |||||
Lightning impulse withstand voltage(peak value) | phase-phase, phase-earth | 60 | 75 | ||||
Isolation fracture | 70 | 85 | |||||
Rated current | A | 400 | 630 | ||||
Rated short-time tolerant current(2s) | kA | 12.5 | 16 | 20 | |||
Rated peak tolerant current | 31.5 | 40 | 50 | ||||
Rated short-time tolerant current of grounding circuit (2s) | 12.5×87% | 16×87% | 20×87% | ||||
Rated peak tolerant current of grounding circuit | 31.5×87* | 40×87% | 50×87% | ||||
Combination and separation device Auxiliary and control circuits | Rated voltage | V | DC:110/220 AC:110/220 | ||||
1min power-frequency withstand voltage | 2000 | ||||||
3 | Low voltage unit | Rated voltage | V | 220 | 400 | ||
1minPower frequency withstand voltage main circuit | main circuit | KV | 2.5 | ||||
Control and metering circuits | 2 | ||||||
Control and metering circuits | A | 100-2500 | |||||
Rated short-time tolerant current(1S) | KA | 15 | 30 | 50 | |||
Rated peak tolerant current | 30 | 63 | 105 | ||||
Branch current | A | Based on user needs | |||||
Compensation capacity | kVar | Based on user needs | |||||
4 | Transformer | Rated capacity | kVA | 30-1600 | |||
Impedance voltage | % | 4 | 4.5 | 6 | |||
Tapping range | ±2×2.5% or ±5% | ||||||
Connection Group | Y,yn0 or D,yn11 | ||||||
No-load loss | w | 90-2755 | |||||
Load loss | 600-15300 | ||||||
5 | Rated housing level | 15 | |||||
6 | Protection level | IP33D | |||||
7 | Noise | dB | ≤50 |
Technical features and advantages:
a. The pre-installed substations can shorten the construction time and reduce costs.
b. Deeply to load center, the substation can improve power supply quality and reduce line losses.
c. The high voltage room, low voltage room, and transformer room are integrated, occupying a small area.
d. The appearance has various styles and beautiful shapes, which is coordinated with the surrounding environment.
e. The new internal structure achieves organic unity of material conservation and performance improvement, with smooth operation and convenient maintenance.
f. Adopting redundant design, there is a secondary backup interval left in the low-voltage section, which facilitates the installation of power monitoring equipment for the power supply department (such as remote meter reading devices, load control devices, distribution transformer comprehensive testers, etc.).
g. With over temperature protection function, to protect the safe operation of the transformer.
h. The dedicated pressure relief channel in the high-pressure chamber ensures the safety of nearby personnel in case of internal arc.
i. The shell adopts a fully assembled design. With a brand new shell coating, the company guarantee colourfast in five years and non-corrosion in ten years.
j. Flexible and diverse solutions and designs can meet the diverse needs of users.